Where safety glass is required in a Melbourne home

The housing code requires safety glass where someone is most likely to walk into or fall against glass. In a house, that means glass in doors, panels right beside doors, glass that starts less than half a metre off the floor, full height panels that look like an opening, and kitchen or bathroom glass that starts less than 2 m above the floor, bath or shower base.

If your window quote lists toughened glass on some panes, laminated on others and nothing on the rest, the table below shows which openings the code covers. The measurements in the table are taken from the visible sight line of the glass, the reference line the code uses.

LocationWhen safety glass is neededClause
DoorsGlass in a door, using a type, thickness and pane size allowed by Table 8.4.2, with separate rules for unframed doors8.4.2
Panels beside a doorThe nearest vertical sight line is less than 300 mm from the doorway, unless an exception applies8.4.3
Full height panelsThe panel could be mistaken for an open doorway, unless an exemption applies8.4.4
Low windows and panelsThe lowest sight line is less than 500 mm above the floor, unless an exception applies8.4.5
Kitchens, bathrooms, ensuites and spa roomsThe lowest sight line is less than 2.0 m above the floor, the bottom of the bath or the shower base, unless an exemption applies8.4.6

Which rules apply to a Victorian house

These requirements sit in Part 8.4 of the ABCB Housing Provisions Standard 2025, the code pathway for houses. Victoria adopted NCC 2025, the National Construction Code, on 1 May 2026. Your designer and building surveyor confirm which edition, building class and compliance pathway apply to your project.

Adopting NCC 2025 does not mean every existing window in Victoria must be upgraded. Replacement windows and alterations may need a project-specific assessment. If alterations made within three years cover more than half the home’s original volume, the whole house can need to be brought up to the current regulations, so ask your building surveyor about your job.

Apartments are commonly Class 2 buildings covered by Volume One of the code, so the Housing Provisions should not be applied to them. A bushfire-prone block also brings separate glass requirements, which our post on BAL-rated windows for bushfire zones explains.

Toughened, laminated and Grade A safety glass

Safety glass is graded, and most of the clauses below call for Grade A safety glazing material. A quote may list either of two types:

  • Toughened glass is heat-treated. It breaks into small, blunt pieces and the whole pane clears from the frame.
  • Laminated glass is two sheets bonded to a plastic layer. When it breaks, the pieces stay stuck to that layer and the sheet stays in the frame.

A framed door can meet the requirement with either type, so the choice is about what you want to happen after a break. That is why laminated glass comes up when security is the concern. Its plastic layer also helps damp some traffic noise. We compare the two in our post on what makes a sliding door hard to force open.

Doors and the glass beside them

White glazed entry door with a narrow fixed sidelight beside the handle.

Clause 8.4.2 covers glass in doors, including French, sliding, stacker and bifold doors. Its Table 8.4.2 sets which safety glass types and thicknesses can be used, and the largest pane allowed for each. The clause allows ordinary annealed glass in a door only for small leadlight pieces and small panels within set size limits. An unframed glass door, other than a shower or bath door, must be toughened or laminated toughened safety glass at least 10 mm thick.

Under clause 8.4.3, a side panel next to a door needs safety glass when its nearest vertical sight line is less than 300 mm from the doorway. Leadlight panels, and small annealed panes whose lowest sight line is more than 1.2 m above the floor, are the exceptions. A panel set further away is judged under the other clauses, such as its height above the floor.

If you are planning new doors, our uPVC double glazed doors page shows the styles these clauses apply to.

Windows that start close to the floor

Lower edge of a white-framed picture window set just above a timber living-room floor.

Clause 8.4.5 covers framed glass where the lowest sight line is less than 500 mm above the floor. A living room picture window with a low sill is one example.

There is one exception. Annealed glass, the ordinary kind, can be used if it is at least 5 mm thick and the pane is no larger than 1.2 square metres.

Height above the ground outside is a separate matter. An upstairs window may also need protection against falls, which is a different rule, and choosing safety glass does not settle it. Our post on whether upstairs bedroom windows need a restrictor covers that rule.

Full height glass you could walk into

Clause 8.4.4 covers glass panels that could be mistaken for an open doorway. It does not apply if any one of these is true:

  • The clear opening is no more than 500 mm wide.
  • The lowest sight line is 500 mm or more above the floor.
  • Transoms or motifs make the glass obvious.
  • A chair rail or handrail at least 40 mm thick is fitted at a height of at least 700 mm.
  • The floor levels on either side of the glass differ by more than 1,000 mm.

Where glass in a door, a side panel or a full height panel is not made obvious by transoms, motifs or similar treatment, clause 8.4.7 requires an opaque band across it, unless one of that clause’s own exemptions applies, such as a pane no more than 500 mm wide. The code’s explanatory note says this marking is not a substitute for safety glass.

Kitchens, bathrooms, ensuites and spa rooms

Clause 8.4.6 covers glass in kitchens, bathrooms, ensuites and spa rooms. Safety glass is needed where the lowest sight line is less than 2.0 m above the floor, the bottom of the bath or the shower base. Glass with any edge exposed, such as a frameless shower screen, must be toughened safety glass at least 6 mm thick.

The clause also sets out exemptions for some mirrors and splash-backs, each with its own conditions. Your designer or building surveyor applies those to the actual layout. If privacy rather than safety is the question, our casement windows room-by-room guide covers obscure glass for bathrooms.

Checking the mark on installed glass

Safety glass installed under Part 8.4 must carry a permanent etch or a label that cannot be reused. A missing sticker does not, on its own, tell you what the glass is. Our post on what to check after new windows are installed explains what the mark shows.

Reading the safety glass lines on a window quote

A clear quote lists the glass for each opening. Before you accept one, check these points against your plans:

  • Each door, and any panel within 300 mm of a door, is listed with safety glass.
  • Each low pane, full height panel, kitchen pane and bathroom pane on your plans has its glass type listed.
  • Each safety glass line names the type, toughened or laminated, and the grade.

If a line is unclear, ask for the glass specification for each opening in writing before you accept the quote.

When you are ready, send your plans or current quote through our contact page, which takes a file upload, and ask Weatherall Windows for a quote that names the glass type for every opening.

The clause detail above is from Part 8.4 of the ABCB Housing Provisions Standard 2025, checked in November 2026. The National Construction Code 2025 was provided by the Australian Building Codes Board under the CC BY 4.0 licence.

Frequently asked questions

Do I have to replace the glass in my existing windows?

A change of code edition does not, by itself, send anyone back to re-glaze a finished home. When you replace windows or alter the house, the building surveyor for that job can tell you what the new work needs, and whether a large alteration brings the whole house under the current rules.

Do apartments follow the same safety glass rules?

No. Apartment buildings are generally assessed under a different volume of the National Construction Code, so the house clauses here are the wrong reference.

Is toughened or laminated glass better?

In framed windows and doors, both can meet the requirement, so neither is better on compliance alone. Pick toughened if you are happy for a broken pane to clear the opening, and laminated if you want it to stay put.